Switches & Relays (WHO = 1, WHO = 4, WHO = 9 & WHO = 25)

The MyHOME integration provides switch entities across three OpenWebNet families:

  1. On/Off Relay Actuators (WHO = 1): Socket outlets, contactors, pumps, and appliance relays declared under switch: in /config/myhome.yaml.
  2. Probe-less Thermo Actuators & Towel Warmers (WHO = 4): F430/2 and F430/4 thermoregulation relays configured via the UI Config Subentry flow (Add thermo actuator / towel-warmer switch (WHO 4)) or switch: in /config/myhome.yaml.
  3. Contact Polarity Toggle (WHO = 9 & WHO = 25): Per-device Invert state configuration switches (EntityCategory.CONFIG) created automatically alongside every WHO = 25 dry contact and WHO = 9 auxiliary binary sensor.

🚀 How WHO = 1 Relays Are Discovered vs Declared as Switches

OpenWebNet WHO = 1 bus frames (*1*0*WHERE## / *1*1*WHERE##) carry no hardware metadata distinguishing a ceiling light relay from a wall socket or extractor fan relay. Because switch.py sets listen=False, unconfigured WHO = 1 addresses seen on the SCS bus are auto-discovered as light.* entities, never automatically as switch.*.

To expose a WHO = 1 relay as a switch.* entity (suppressing the duplicate light.* entity on that address), declare it under switch: in /config/myhome.yaml:

# /config/myhome.yaml
switch:
  kitchen_counter_socket:
    where: "14"
    name: Kitchen Counter Socket
    class: outlet

Note

Single-Gateway vs Multi-Gateway myhome.yaml Layout: Flat top-level switch: blocks apply to single-gateway installations. On multi-gateway installations, nest switch: (and any other domain blocks) under each gateway's MAC address key (e.g. "00:03:50:01:02:03":).


🔌 Displaying Relays as Outlets, Valves, or Fans ("Show As")

Once a relay is declared under switch: (with optional class: outlet or class: switch), you can also refine how Home Assistant presents it in the UI using "Show As":

  1. Open Home Assistant and navigate to Settings → Devices & Services → Entities.
  2. Select your switch entity (e.g. switch.kitchen_counter_socket).
  3. Click the Settings (gear) icon.
  4. Under Show As, choose how you want the entity presented across your dashboards:
    • Switch (Default): Standard relay, appliance, or heater.
    • Outlet: Wall socket / plug load.
    • Fan / Valve / Light: Helper wrapper around the underlying switch.
  5. Click Update. Home Assistant immediately converts the entity representation across Lovelace dashboards, voice assistants (HomeKit, Alexa, Google Assistant), and automations.

⏱️ Native Hardware Bus Timers

Like MyHOME lights, physical SCS WHO = 1 switch relays can run native hardware timers directly on the bus (myhome.turn_on_timed applies to individual WHO = 1 relays and refuses WHO = 4 thermo switches and WHO = 9/25 invert switches). This ensures that pumps, heaters, or ventilation relays turn off after the elapsed time regardless of whether Home Assistant is running:

action: myhome.turn_on_timed
target:
  entity_id: switch.bed_heating_pad
data:
  duration: 1800   # Turn on and automatically turn off after 30 minutes (1800 s)

🔀 Master / Slave (M=SLA) Actuators vs Decoupled Independent Control

In traditional physical SCS configuration, auxiliary loads like bathroom extractor fans or secondary contactors are often configured as slaves by inserting M=SLA (or delayed-off configurators M=1..4) and duplicating the master actuator's A and PL address.

Warning

OpenWebNet Limitation with M=SLA: On the physical bus, an actuator in M=SLA does not have its own independent OpenWebNet address. It listens to the identical A*PL broadcast telegram as its master. Sending an OpenWebNet frame (*1*1*APL##) turns on both the master and slave simultaneously. It is not possible to control an M=SLA slave independently from Home Assistant without also triggering the master.

Instead of wiring two relays in parallel or keeping M=SLA:

  1. Remove M=SLA: Configure the auxiliary relay (e.g. Channel 2 of an F411/2 or F411/4) with its own distinct PL address (e.g. Light = 11, Fan = 12, with M left empty).
  2. Declare as Switch: Declare address 12 under switch: in /config/myhome.yaml (switch.bathroom_fan) and optionally wrap it as a Fan via Home Assistant's Show As setting.
  3. Automate the Overrun in HA: Use an automation to turn on the fan when the light turns on, and run an overrun timer (myhome.turn_on_timed) or humidity purge when the light turns off.

See the complete guide and YAML configuration in Use Cases — Decoupled Bathroom Extractor Fan.


🔥 Probe-less Thermo Actuators & Towel Warmers (WHO = 4)

Bathroom towel warmers and electric radiant relays are often wired to F430/2 or F430/4 thermoregulation actuators (WHO = 4, e.g. Zone 7, Actuator 1 → WHERE = 7#1) without a room temperature probe.

  • No Phantom Climate Entities (Safe Coexistence with Real Thermostats): Actuator-only Dimension 20 status frames (*#4*7#1*20*0/1##), pure-valve Dimension 19 status frames (*#4*7*19*0*0/1## on configured Z#N zones), and circulation-pump demand/release notifications (*4*4001*...## / *4*4002*...##) no longer spawn broken temperature-less climate entities. Configuring a per-actuator switch (WHERE = 7#1) prunes any temperature-less ghost climate entity on that zone while preserving any real thermostat that reports temperature or mode on the same zone; configuring a zone-wide switch (WHERE = 7) claims the entire zone unless climate: is also explicitly configured.
  • UI Configuration (Recommended): Navigate to Settings → Devices & Services → MyHome, click Add thermo actuator / towel-warmer switch (WHO 4) on your gateway, and enter WHERE (e.g. 7#1 for actuator 1 of zone 7, 7 for the whole zone, or 7#1#4#01 behind an F422 bus interface).
  • Direct Dimension 20 Control (turn_on_command / turn_off_command left blank): When left blank, Home Assistant sends *#4*7#1*#20*1## / *#4*7#1*#20*0## and tracks live relay state in real time from both *#4*7#1*#20*0/1## bus writes and *#4*7#1*20*...## status replies (plus state restoration across restarts). Although the public OpenWebNet WHO = 4 specification lists Dimension 20 as read-only, emulated gateway firmwares (F454, MH200N, F459, F460, F461) and real MyHomeServer1 hardware translate #20 writes onto the SCS bus ($0496813100\r / $0496813101\r; H4684 and MH200 drop Dimension 20 frames). If your gateway or actuator ignores direct #20 writes, bind paired CEN+ or WHO = 1 scenario triggers instead.
  • MyHomeServer1 (Home + Project "Towel Warmer"): On MyHomeServer1, bt_thermo_manager actively locks Home + Project Towel Warmer (BNTR) objects and immediately reverts direct *#4*Z#N*#20*1/0## bus writes unless towel.setSync is invoked by a Home + Project / Home + Control Scenario or Automation. Create two Scenarios (Turn Towel Warmer ON and Turn Towel Warmer OFF): important — when adding the Towel Warmer to a Scenario's action list in Home + Project or Home + Control, its default action state is OFF (*#4*Z#N*#20*0##); tap the Towel Warmer item inside the ON scenario's action list to toggle its target state to ON (or select a boost duration) before saving. Because app-only scenarios do not allocate an OpenWebNet Scene_Address entry in MyHomeServer1, bind the two scenarios to any of the following triggers (even when every visible wall switch plate is already in use) and enter the corresponding frames in turn_on_command and turn_off_command:
    1. Unpopulated button slots on existing SCS modules (WHO = 25 CEN+, zero wall keys lost): 2-module pushbuttons (H4652/2, L4652/2, K4652M2, LN4652, KW8010/8011/13) fitted with a single-rocker keycap and flush 2-channel actuator-controls (H4672M2, LN4672M2, K4672M2L) mounted behind blind covers or in junction boxes expose unused button slots in Home + Project that can be bound to CEN+ scenarios (e.g. *25*21#1*21## for ON and *25*21#2*21## for OFF) without changing any physical wall keycap.
    2. A single unwired relay terminal (WHO = 1, only 1 channel needed): Register one unwired output terminal on any multi-channel actuator (F411/4, F411/2, K8002L, etc.) as a light/socket in Home + Project (e.g. WHERE = 09 in a technical room) and trigger the ON scenario when 09 turns ON (*1*1*09##) and the OFF scenario when 09 turns OFF (*1*0*09##).
    3. Zero-SCS-slot fallback (emulated_hue): If every button slot and relay terminal on the SCS bus is occupied, pair Home Assistant's built-in emulated_hue bridge as a local Philips Hue light (BN3L) in Home + Project and trigger the ON/OFF scenarios from that virtual light.
# Optional YAML equivalent in myhome.yaml:
switch:
  bathroom_towel_warmer:
    who: "4"
    where: "7#1"
    name: Bathroom Towel Warmer
    # Optional — required on MyHomeServer1 Home + Project BNTR Towel Warmers
    # (or on gateways like H4684 / MH200 that drop Dimension 20 writes):
    turn_on_command: "*25*21#1*21##"
    turn_off_command: "*25*21#2*21##"

🔄 Legacy YAML Import & Multi-Gateway Note

Note

Validated switch: entries in /config/myhome.yaml are automatically imported and cached into the gateway's config entry options (migrated_yaml_platforms) so WHO = 1 relays remain switch.* entities even if /config/myhome.yaml is later removed. On multi-gateway setups, place switch: under each gateway's <MAC>: header. For migrating pre-v0.9 configuration.yaml files, see the Legacy YAML Migration Guide.