Climate Configuration (v0.9.x YAML)¶
[!WARNING] Legacy Configuration: This page describes manual YAML configuration in
/config/myhome.yamlused by MyHOME v0.9.x. In MyHOME v2.0+, thermoregulation zones are discovered directly from the bus.
Climate entities are developed for OpenWebNet WHO = 4 (Thermoregulation).
Depending on whether your physical installation uses a 99-zone central unit, a 4-zone central unit, or standalone zone probes, choose the matching structure below:
1. 99-Zone Central Unit (3550)¶
In a 99-zone setup, the physical central unit has the special address #0, and all subordinate zones have their own zone number with standalone: false:
zone: The zone address ('#0'for the central unit,'1'..'99'for zones).heat: Optional boolean (defaulttrue), set totrueif the zone supports heating.cool: Optional boolean (defaultfalse), set totrueif the zone supports cooling.standalone: Must be set tofalsein a 99-zone architecture.
f454:
mac: '00:03:50:xx:xx:xx'
climate:
central_unit:
zone: '#0'
name: Central Unit
heat: true
cool: false
standalone: false
manufacturer: BTicino
model: 3550
zone_1:
zone: '1'
name: Living room
heat: true
cool: false
standalone: false
manufacturer: BTicino
model: F430/4
2. 4-Zone Central Unit (HC4695, L4695, LN4691)¶
In a 4-zone setup, the master unit acts simultaneously as the central coordinator and as zone 1 (central: true):
f454:
mac: '00:03:50:xx:xx:xx'
climate:
central_unit:
zone: '1'
name: Central Unit Living Room
heat: true
cool: false
central: true
standalone: false
manufacturer: BTicino
model: HC4695
zone_2:
zone: '2'
name: Bedroom
heat: true
cool: false
standalone: true
manufacturer: BTicino
model: F430/4
3. Standalone Probes (No Central Unit)¶
If you have independent chronothermostats or probes (H4691, LN4691) operating autonomously without a central unit, configure each as standalone: true: