Skip to content

Gateway Identification

How MyHOME decides which gateway model you have, why that matters, what evidence it uses, and how to check the result in your own traces.

TL;DR — The model label comes from the gateway's own UPnP/SSDP announcement or from your choice in the config flow. The in-band WHO=13 "model request" reply can only confirm or question that label, because its official code table dates from 2006 and does not know any gateway sold since. When that reply is a code shared by several modern gateways (200), the integration asks a second question, WHO=1013 dimension 1 (OBJECT_MODEL), whose catalogue is one code per model, and lets that answer settle it. Every diagnostics download and bus-monitor export carries an identification block that shows exactly how the label was established.


Why the label matters

The model name is not cosmetic. It selects the gateway profile in the OWNd protocol engine, which drives:

Profile setting Example: MH200 / MH200N Example: MyHOMEServer1
concurrent command sessions 1 4 (2 by default)
pacing between commands 150 ms 20 ms
command queue size 100 300
subsystems queried at startup lighting, automation, heating, CEN, scenarios all, incl. audio and energy
HMAC (SHA) authentication no yes

A gateway labelled as a faster model than it is gets flooded; one labelled as a slower model is throttled for nothing. The label also lands in the entry title, the device registry, diagnostics and every trace attached to a bug report — so a wrong label misleads the people trying to help you.


The three sources of a model label

source Where it comes from Trust
ssdp The gateway announced its own modelName over UPnP/SSDP when it was discovered (F454, F455, MH200N, MH202, MyHomeServer1 …). Authoritative — the device said so itself.
manual You typed the address and picked the model in the config flow. Trusted, but correctable by certain evidence — early versions of the manual flow defaulted to F454, which produced mislabelled entries.
who13 No model was configured; the entry was labelled from the WHO=13 reply (see below). Best effort.

What the bus can tell us: WHO=13 dimension 15

Gateways answer the model request *#13**15## with *#13**15*<code>##, and most broadcast it periodically on the monitor session. The only official meaning of <code> is BTicino's OpenWebNet_Community_2_device v1.0.0 (13 June 2006), section 1.2.6 — and that table is complete at six entries:

code model era
2 MHServer 2005
4 MH200 2006
6 F452 2006
7 F452V 2006
11 MHServer2 2006
13 H4684 2006

That is the whole list. F454, F455, MH200N, MH201, MH202, MyHOMEServer1, F461 … are not in it. Newer gateways reuse an old code or invent one, so the reply can corroborate a label but can never establish one for a modern gateway. The MH200N is the exception that has a code of its own: 44 in the WHO=1013 catalogue and in Nmap's WHO=13 table (below). A gateway answering the 2006 code 4 is therefore an MH200, not an MH200N: a physical MH200 (firmware 2.1.0) answers *#13**15*4##, and until 2026-09-23 a manual MH200N label on one was wrongly accepted as the same family.

Codes seen in the field (evidence, not specification)

code seen on evidence
16 F453 Confirmed on physical BTicino F453 in Discussion #856 (firmware 2.0.10, kernel 2.3.8, ETLinux 3.0.1; UPnP modelName F453). Corroborates Nmap's 2017 table (WHO=1013 catalogue calls the same model 42, though firmware 2.0.10 echoes 16 on WHO=1013 too).
23 H4684 / H/L4684 / L4684 Confirmed on physical BTicino H/L4684 touchscreen gateway in #466 (firmware 6.0.11, kernel 2.6.2, distro 6.0.0; UPnP modelName H/L4684), distinct from the 2006 specification code 13 on firmware 2.0.54.
200 F454 / MyHOMEServer1 / MH202 / F461 / H4890 / MH201 Confirmed on physical hardware in #420 for the F454 (firmware 2.0.51), the MH202 (1.0.21) and the MyHomeServer1 (2.87.13), in #466 for the H4890 (4.0.15) and F461 (2.0.11), and on the MH201 (3.3.6 / 3.6.27). Shared across modern gateway families, so it identifies none of them — it is the cue for the WHO=1013 question below.

Codes from an independent implementation

Nmap's openwebnet-discovery.nse has carried a device table for this very dimension (device_dimension["Device Type"] = "15") since the script was first committed on 2017-07-18 — years before this project. Beyond the six official codes and 16 (F453), 23 (H4684), and 200 now confirmed on physical hardware above, it adds five more codes that the integration recognises:

code model note
12 F453AV
15 F427 Nmap writes "F427 (Gateway Open-KNX)"
27 L4686SDK
44 MH200N
51 F454 see below

Nobody here has seen these on a bus, so they rank below field evidence: they can label a gateway that has no model and corroborate one that has, but they never contradict your configuration.

51 is the interesting one. Nmap listed it as F454 in 2017 and, separately, the OpenWebNet device database quoted in #420 says the same — two unrelated sources, neither of them a capture. Nmap also labels 200 as "F454 (new?)", which suggests 200 was the newcomer at the time.

A theory, not a finding. The F454 may straddle two schemes: early/1.x firmware answering the concrete 51, later/2.x firmware answering the generic 200 and leaving the specific identity to WHO=1013 OBJECT_MODEL 51. The traced F454 in #420 runs firmware 2.0.51 and does answer 200 then 51. But no 1.x unit has ever been captured — a 2.x F454 cannot be downgraded to check — so nothing in the code depends on this being true.

If your gateway reports a code that is in none of these tables, the integration logs it, keeps your configured model, and surfaces an unknown_gateway_model repair issue asking for a diagnostic trace.

Step 2 — WHO=1013 dimension 1 (OBJECT_MODEL) settles a shared code

A shared code such as 200 cannot label an unconfigured gateway, and it cannot check an SSDP or manual label either. So whenever WHO=13 answers a shared code — whatever the source of the configured model — the integration sends one status request on the command session:

*#1013**1##             → *#1013**1*<OBJECT_MODEL>##

WHO=1013 is the Gateway Diagnostic family (Nmap's table of WHO values calls it Device Diagnostic); dimension 1 is the model code, and its catalogue has one code per model (4 MH200, 5 MH202, 19 H4684, 26 LGRH4684, 44 MH200N, 51 F454, 67 MyHOMEServer1, 134 F461, … — the full list is WHO1013_OBJECT_MODELS in const.py, taken from the OpenWebNet device database as listed in #370, with H4684 and LGRH4684 confirmed via firmware reverse-engineering). A real reply is four values, not one — OBJECT_MODEL, N_CONF, BRAND, LINE (per the OpenWebNet Encyclopedia's work on MHCatalogue.db, via @anotherjulien in #420):

*#1013**1*67*15*5*0##   ← MyHomeServer1 (firmware 2.87.13)
*#1013**1*51*15*5*0##   ← F454 (firmware 2.0.51)
*#1013**1*5*15*5*0##    ← MH202 (firmware 1.0.21)
*#1013**1*16*0*1*0##    ← F453 (firmware 2.0.10, via myhome.sweep_bus)
         │   │  │ └── LINE  = 0, "Undefined"
         │   │  └──── BRAND = 5 ("Legrand BTicino") or 1 ("BTicino")
         │   └─────── N_CONF = 15 (modern gateways) or 0 (F453)
         └─────────── OBJECT_MODEL

Modern 200-class gateways traced so far answer *15*5*0 (N_CONF 15, BRAND 5 "Legrand BTicino", LINE 0 "Undefined"), whereas the legacy ETLinux 3.0.1 F453 (2.0.10, Discussion #856) answers *#1013**1*16*0*1*0## when explicitly queried by myhome.sweep_bus — echoing its WHO=13 device type 16 (documented in WHO1013_OBSERVED_OBJECT_MODELS as field evidence alongside MHCatalogue.db's 42) with N_CONF 0 and BRAND 1 ("BTicino" in MHCatalogue.db EN_BRAND). N_CONF 15 lies outside the ordinary 0..12 physical-configurator range and looks like the 0xF sentinel, so its gateway-specific meaning stays unresolved. Only OBJECT_MODEL decides the identity; N_CONF, BRAND and LINE are recorded and travel in diagnostics. Note that the same product does not necessarily answer matching codes in the two families: an F454 is 51 here but 200 (or 51 on 1.x firmware) on WHO=13. The two tables are therefore kept apart, and the WHO=1013 one is consulted automatically only after a shared WHO=13 code.

One product, two brand names

Some catalogue entries carry more than one name — 51 is F454 and 003598. These are not order codes or sub-models: BTicino sold the device as F454, Legrand sold the same hardware as 003598, and nowadays Legrand mostly uses the BTicino names (@anotherjulien). The integration therefore:

  • always displays the BTicino name, and never treats the other as a separate model;
  • still accepts the other name, so a gateway announcing 003598 over SSDP is corroborated by OBJECT_MODEL 51 rather than flagged as a mismatch;
  • lists the alternatives in diagnostics as who1013_other_names, so an owner whose box says 003598 can see why their device page says F454.

In principle the BRAND field could choose which name to show. It cannot on modern shared-code gateways: they answer 5, "Legrand BTicino", which covers both houses (1, "BTicino", has so far only been observed on the legacy BTicino-only F453).

Two safeguards keep this off legacy hardware and out of your logs:

  • A legacy gateway never gets the question. An MH200 answers 4 on WHO=13, which is unambiguous, so the WHO=1013 request is never queued (verified on a physical MH200; there is a regression test for it). Only gateways that answer a shared code are asked, and those are all modern Linux gateways that implement WHO=1013.
  • A gateway that does not answer costs nothing visible. The request goes out as a status request: if the gateway NACKs it, OWNd retries once and logs both attempts at DEBUG. One request is sent per answer: while it is unanswered the periodic re-broadcast of the shared code does not repeat it, and a reconnect of the event session is what gives it another try.

What the answer does depends on the configured source and whether the OBJECT_MODEL comes from the diagnostic catalogue (WHO1013_OBJECT_MODELS, certain) or from field evidence (WHO1013_OBSERVED_OBJECT_MODELS, uncertain), mirroring the WHO=13 rule below: a catalogue OBJECT_MODEL labels an unconfigured gateway, corrects a manual choice (with a Gateway model corrected issue), and cross-checks an SSDP identity — which is never overruled, but a Gateway model mismatch issue asks you to confirm when the two disagree; a field-observed OBJECT_MODEL (16 on F453) labels an unconfigured gateway and corroborates a matching model without contradicting another configured model or masking a certain WHO=13 specification reading. Within the same certainty tier, WHO=1013 outranks WHO=13, so the periodic re-broadcast of the shared code that started the check cannot undo its verdict; only a later WHO=1013 reply changes it. An OBJECT_MODEL in neither table raises the same unknown_gateway_model issue as an unknown WHO=13 code, with the code written as 1013-1-<value>.

How the verdict is reached

Each source is recorded separately — what you picked, what the gateway announced, the WHO=13 code, the WHO=1013 code — and one pure function (resolve_gateway_identity in identity.py) turns all of it into the effective model plus its corroboration or conflict state. The handlers only answer "what did I observe?"; a single resolver answers "what should the integration believe?". Because the same evidence always yields the same verdict, a repeated broadcast can neither repeat a correction nor flap a repair issue.

Hardware version is deliberately not requested. Nmap's table calls WHO=13 dimension 17 "Hardware Version", and it is documented as such for the Zigbee part of OpenWebNet, with the same three-digit V.r.b shape as the firmware version. It has never been canonically described for non-Zigbee OpenWebNet (@anotherjulien) — it is probably the same thing, but "probably" is not evidence, so the integration neither asks for it nor fills the device page's hw_version from it.

The two families are separate number spaces. They are not two spellings of the same identifier, and the same model carries different numbers in each: an F453 is 42 in the WHO=1013 catalogue (though firmware 2.0.10 echoes 16 on WHO=1013 as well) vs 16 on WHO=13, and an H4684 is 19 (or 26 for Legrand LGRH4684) against 13 (2006) or 23 (firmware 6.0.11 / Nmap). Several values do coincide — 4, 12, 44, 51 — which is precisely why the tables are kept apart instead of merged on the ones that agree; a test pins both the overlaps and the clashes.

Status of the evidence. Eight gateways are verified on real hardware, with fixtures replayed by the test suite: the MH200 answers 4 (mh200_physical_plant), the F453 answers 16 on WHO=13 and 16 on WHO=1013 when swept (discussion_856), the H/L4684 (6.0.11) answers 23 (issue_466), and the F454, MH202, MyHomeServer1, F461, and MH201 answer the shared 200 and then 51, 5, 67, 134, and 10 (pr_420_f454, pr_420_mh202, pr_420_myhomeserver1 in #420, issue_466_f461, and issue_466). Still untraced on live hardware: the claim that a 1.x F454 answers 51 on WHO=13, whether another F453 firmware answers MHCatalogue.db's 42 on WHO=1013, and the remaining catalogue codes (H4890 200 has a sweep without WHO=1013, and H4684 19 / LGRH4684 26 are confirmed via firmware emulation). If you own one of those, the who1013_code field in your diagnostics download (below) is the evidence we are missing — please attach it to an issue.


Setup time: a manually added gateway is asked who it is

The manual form (Custom (IP Gateway) → address → MAC and model) offers defaults that are easy to leave in place: MAC 00:03:50:00:00:00 and model MyHomeServer1. The runtime resolver above corrects the model later, but the MAC is the entry's unique_id and is fixed when the entry is created. So, once the gateway has accepted the password, the config flow opens one command session and asks, in the order the runtime uses:

step request asked when what it settles
1a *#13**15## always (setup & runtime startup) the WHO=13 device type; every known gateway answers it
1b *#13**16## always (setup & runtime startup when firmware is unknown) the gateway firmware version (V.R.B), which also gates firmware-specific profile capabilities (e.g. H/L4684 FW ≥ 6.0.0)
2 *#1013**1## only when step 1a returned a shared code (200) the OBJECT_MODEL, one code per model
3 *#13**12## (MAC) setup only, when every model the codes can name is in MAC_REQUEST_SAFE_MODELS the gateway's real MAC

The whole probe is best effort with a 15 s cap: a gateway that refuses the session, answers nothing or times out leaves the typed values in place.

The MAC request is gated, and the gate fails closed. A real H4684 (020054) and a real MH200 (020102) daemon crash on *#13**12## (own-firmware-oracle, real-binary runs); the F459 / F460 / F461 / MyHomeServer1 factory images answer *#13**12*0*0*0*0##, and the F450 / F454 / MH202 images answer with the interface's bytes. Only a model a physical unit answered with its real MAC is in MAC_REQUEST_SAFE_MODELS (config_flow_discovery.py): the F461 (firmware 2.0.11) and the MyHomeServer1 (3.87.13), both captured in the tests/fixtures/traces live runs. An unknown, unlisted or merely emulated-without-crash model is never asked, and when the gate stays closed the typed MAC stands. The list is meant to move into an OWNd profile flag once the oracle rows are published.

What the answers do:

  • MAC — the reply must pass the same validation as the form (six octets, 0..255) and must not be the all-zero factory value 00:00:00:00:00:00 (also the first form's Custom sentinel) or the broadcast address; otherwise the typed MAC is kept and the reply is logged at DEBUG. A usable MAC that differs from the typed one replaces it and becomes the unique_id. The unique_id is set only at this point, so a second gateway typed with the placeholder MAC is not refused before it could report its real one; a true duplicate still aborts with already_configured.
  • Model — the codes go through the same resolve_gateway_identity as at runtime: a certain code (2006 table or WHO=1013 catalogue) corrects the chosen model, a brand variant of the reported model (H4890 for OBJECT_MODEL 30, 003598 for 51) is kept, an uncertain code (WHO=13 or WHO=1013 field evidence / third-party table) may label a Generic entry but never overrides a chosen model. A corrected model also changes the OWNd profile, the entry title and the default number of command workers, and the entry records model_source: who13 so the diagnostics block below reports it.
  • Split authentication — a gateway whose monitor session (*99*1##) is open but whose command session (*99*0##) wants a password answers the probe with password_required; the flow then asks for the password (the runtime command workers need it anyway) and probes again with it. The probe's own OWNd log lines are recorded at DEBUG.

A gateway discovered over SSDP is not probed: its identity is authoritative.


The rule the integration applies

When a dimension-15 reply arrives, the handler compares the reported model with the configured one. A configured model that one of the tables lists by name has a code of its own, so only that name or a brand variant of it agrees: MH200N (44) is contradicted by 4 (MH200), and F452V (7) by 6 (F452), even though each pair shares a family. A name no table lists is compared by family (F452X → F452), so an unlisted variant suffix is never downgraded. Then:

configured source code agrees code contradicts — official 2006 code code contradicts — uncertain code (field evidence or third-party) code shared (200) code unknown
ssdp nothing model kept; repair issue asks you to confirm model kept, no repair issue model kept; WHO=1013 asked and its answer cross-checks (mismatch → repair issue asks) recorded; repair issue created
manual nothing model, profile and device registry corrected; repair issue tells you model kept, no repair issue model kept; WHO=1013 asked and its answer corrects if it differs recorded; repair issue created
none / who13 — labelled from the code labelled from the code WHO=1013 asked and its answer labels recorded; repair issue created

"Contradicts — uncertain code" covers both field evidence and the third-party table: neither can prove your gateway is something else, so the configured model stands untouched.

Two repair issues exist for this:

  • Gateway model mismatch for … (gateway_identity_mismatch) — the reported and configured models disagree and the integration is not sure enough to act. It names the code, what the specification or field evidence says it means, and how to fix it via Configure (Options Flow; Reconfigure updates host/port/password) if the reported model is what you own.
  • Gateway model corrected to … (gateway_identity_corrected) — a manually chosen model was contradicted by an official 2006 code or by a catalogue WHO=1013 OBJECT_MODEL and was corrected; open Configure (Options Flow) if you need to override the model manually.

Neither issue is raised twice for the same finding, and a mismatch issue is withdrawn automatically if the gateway later reports a code that no longer contradicts.


What the device page shows

Settings → Devices & services → MyHOME → the gateway device:

field where it comes from
Model the resolved identity — SSDP or your choice, corrected or labelled by WHO=13 / WHO=1013 as described above. Always the BTicino name.
Model ID the OBJECT_MODEL number from WHO=1013 (51 for an F454). The only model identifier the gateway ever states about itself; absent until the gateway answers (automatically when WHO=13 returned a shared code, or when myhome.sweep_bus queries *#1013*0*1##).
Firmware WHO=13 dimension 16.
Serial number the gateway's serial as reported by the connection (the MAC for TCP gateways).
Manufacturer the entry's manufacturer, normally BTicino S.p.A.. Not taken from the BRAND field, which does not distinguish the two houses.

N_CONF, BRAND, LINE and the alternative brand name are not on the device page — none of them identifies the hardware, and brand only repeats the manufacturer. They are in the diagnostics download instead.

Check it yourself

Every diagnostics download (Settings → Devices & services → MyHOME → ⋮ → Download diagnostics) and every bus-monitor export (Export Trace / Export Sweep) carries:

"identification": {
  "model": "MH200",
  "source": "manual",
  "configured_model": "MH200",
  "ssdp_model": null,
  "who13_code": "4",
  "who13_model": "MH200",
  "who13_model_official": "MH200",
  "who13_model_observed": null,
  "who13_firmware": null,
  "who13_kernel": null,
  "who13_distribution": null,
  "who1013_code": null,
  "who1013_model": null,
  "who1013_other_names": [],
  "who1013_n_conf": null,
  "who1013_brand": null,
  "who1013_line": null,
  "profile": "MH200Profile",
  "conflict": null
}

Reading it:

  • source — which of the three sources produced the label.
  • who13_code — the raw code your gateway reported; who13_model_official / who13_model_observed — what the 2006 specification and the field evidence say it means (either may be null).
  • who13_firmware, who13_kernel, who13_distribution — dimensions 16 / 23 / 24, corroborating evidence when the gateway sends them (*#13**16## is actively queried on startup whenever the firmware version is not yet known).
  • who1013_code / who1013_model — the WHO=1013 OBJECT_MODEL reply and what the diagnostic catalogue or field evidence says it means; both null unless who13_code was a shared code (the question is not asked automatically otherwise) or myhome.sweep_bus queried *#1013*0*1## and the gateway answered. On an MH200 they are always null.
  • who1013_other_names — the same product's other brand name(s), e.g. ["003598"] for an F454.
  • who1013_n_conf, who1013_brand, who1013_line — the rest of the reply, rendered as value (meaning) when the value has been seen before and as the bare value when it has not, so a new one reaches the trace instead of being dropped. Traced gateways show "1 (BTicino)" or "5 (Legrand BTicino)", and "0 (Undefined)".
  • profile — the OWNd profile actually in use (MH200 uses MH200Profile, which disables WHO 22 and WHO 25, distinct from MH200NProfile used by MH200N).
  • conflict — non-null exactly when a Gateway model mismatch repair issue is open, with the reason.

If source is manual and who13_code is not in either table, you are the first to see that code: please open an issue with the export attached.


What to do if your gateway is mislabelled

  1. Open the entry's Configure button (Options Flow) and select the Gateway Hardware Model (name) you own (⋮ → Reconfigure is for host, port, and password). Changing the model in Configure preserves all of your devices and entity IDs.
  2. If you know your model but the integration keeps questioning it, the WHO=13 code your gateway sends is new evidence — attach the export to an issue so the table above can grow.
  3. Never edit custom_components/myhome/const.py on your installation to "fix" a code: the precedence rule above is what protects you from the next mislabel.